Home Addressable Fire SystemsXFP 16 Zone Repeater Panel

XFP 16 Zone Repeater Panel

by Marcus Carter
XFP 16 Zone Repeater Panel

The XFP 16 Zone Repeater Panel from C-TEC can be used to repeat the functions of an XFP Main panel at remote parts of a site (e.g. all potential fire service entrances) and offers all of the functions and controls of an XFP Main panel (access levels 1, 2 and 3).

XFP 16 Zone Repeater Panel Technical Specifications:

  • Includes an on-board fault relay.
  • Requires its own dedicated Mains power and battery back-up supply.
  • A maximum of eight XFP Repeaters can be connected to one non-networked XFP Main panel.
  • Communication between the XFP Main panel and Repeater requires a CFP761 network driver card (fitted as standard in all XFP510-16s, available as an optional extra on Main XFP 16 Zone panels).
  • Repeater network wired in 1.5 mm2 two-core screened fire resistant cable. Network length must not exceed 500 metres
  • Protocol/compatibility Compatible with C-TEC’s XFP CAST, Apollo XP95/Discovery and Hochiki ESP main panels
  • Mains supply 230V 50/60Hz.Mains rated current 350mA maximum
  • Internal power supply 27Vdc nominal
  • Total output current limited to 1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA)
  • Quiescent current TBC
  • Max battery size and type 2 x 12V 3.2Ah VRLA connected in series
  • Auxiliary relays Fault (Failsafe; Capable of switching 1A @ 30V DC; Must not be used for switching Mains voltages)
  • PC connection None
  • Indicators 2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault
  • Expansion connections On board CFP761 network driver card facilitates the connection of additional XFP Repeaters
  • Product dimensions (mm) 380 W x 235 H x D 96mm;Construction & finish Plastic lid and base; RAL7035 textured
  • IP Rating IP30.Weight 1.8kg (without batteries)
  • Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%
  • Network specification Max. no. of Repeaters per Main XFP: 8 (any mix); Max. total length of Repeater network: 500m; Cabling requirements: 1.5mm2 two core screened fire resistant.