935
The XFP 16 Zone Repeater Panel from C-TEC can be used to repeat the functions of an XFP Main panel at remote parts of a site (e.g. all potential fire service entrances) and offers all of the functions and controls of an XFP Main panel (access levels 1, 2 and 3).
XFP 16 Zone Repeater Panel Technical Specifications:
- Includes an on-board fault relay.
- Requires its own dedicated Mains power and battery back-up supply.
- A maximum of eight XFP Repeaters can be connected to one non-networked XFP Main panel.
- Communication between the XFP Main panel and Repeater requires a CFP761 network driver card (fitted as standard in all XFP510-16s, available as an optional extra on Main XFP 16 Zone panels).
- Repeater network wired in 1.5 mm2 two-core screened fire resistant cable. Network length must not exceed 500 metres
- Protocol/compatibility Compatible with C-TEC’s XFP CAST, Apollo XP95/Discovery and Hochiki ESP main panels
- Mains supply 230V 50/60Hz.Mains rated current 350mA maximum
- Internal power supply 27Vdc nominal
- Total output current limited to 1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA)
- Quiescent current TBC
- Max battery size and type 2 x 12V 3.2Ah VRLA connected in series
- Auxiliary relays Fault (Failsafe; Capable of switching 1A @ 30V DC; Must not be used for switching Mains voltages)
- PC connection None
- Indicators 2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault
- Expansion connections On board CFP761 network driver card facilitates the connection of additional XFP Repeaters
- Product dimensions (mm) 380 W x 235 H x D 96mm;Construction & finish Plastic lid and base; RAL7035 textured
- IP Rating IP30.Weight 1.8kg (without batteries)
- Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%
- Network specification Max. no. of Repeaters per Main XFP: 8 (any mix); Max. total length of Repeater network: 500m; Cabling requirements: 1.5mm2 two core screened fire resistant.